Switchgear

SF6 Circuit Breaker

Even in the event of a complete gas leak, our SF6 CBs are capable of breaking 100% normal current & with stand system voltage
Advance warning of gas leak by continuous pressure monitoring
Explosion proof and fail-safe CB by means of safety membrane for each pole
Automatic safety shutters to cover live parts when CB is withdrawn
No degradation of main current carrying contacts, as there are separate currents carrying and arcing contacts
Our SF6 CBs operate at low pressure. The internal pressure rise at the instant of current interruption also stays low. Due to this, and the high degree of gas tightness, adequate for entire life of the breaker is ensured.
Easy retro fitting with cassette system
Fully type tested as per IEC60056/IS 13118/IEC 62271-100
Type 11kV 22kV 33kV
FP62D FP63G FP62D FP63G FP72D FP73D
Rated Voltage kV 12 12 24 24 36 36
Insulation level kVrms/kVp 28/75 28/75 50/125 50/125 70/170 70/170
Rated Current A 1250 2500 1250 2500 1600 1600
Braking Capacity kA 26.2 40 26.2 26.2 16 26.2
Making Capacity kAp 65.5 100 65.5 65.5 40 65.5
Short Time Current(1 or 3 Sec) kA 26.2 40 26.2 26.2 16 26.2
Operating Sequence O - 0.3 Sec - CO - 3 min - CO
Auxiliary Switch Contactse 8NO + 8NC
Spring Charging Motor Power W 250
Spring Charging Motor Voltage V 230V AC, 110V DC, 220V DC
Closing / Tripping Coil Power W 80
Closing / Tripping Coil Voltage V 24, 30, 48, 110, 220DC
Weight (approx) kG 200 225 200 225 225 250
Proven spring operated mechanism
Designed to closed and latch
Manual/motorised option
In built trip free mechanism
In built anti pumping feature
Mechanical ON/OFF indication

Download Brochure

Metal Clad M.V Switchgear.

Product Enquiry: